MINE REELING CABLE
(N)TSCGEWTOES

Spec Sheet

Cable Properties

Fire Retardant

Self Extinguishing

Oil Resistant

Good Chemical Resistance

Water Resistant

Six core cable, comprising two pilots and one protective earth. Meets DIN VDE 0250 part 813; DIN VDE 0295; DIN VDE 0298; DIN VDE 0472; prEN 50363.
1. Conductor
  • Flexible plain copper "FSC" better than IEC 60228 class 5.
2. Insulation
  • Inner semi-conductive layer.
  • New special insulation compound EPDM, better than DIN VDE 207 part 20.
  • Outer semi-conductive layer, easy strip design.
3. Protective Earth Conductor
  • Flexible plain copper "FSE" better than IEC 60228 class 5.
4. Ground Check Conductor (Pilot Core) 5. Inner Sheath Special Synthetic Rubber, better than GM1b. 6. Reinforcement
  • Synthetic threads with very high tensile strength as a protection against twist stress and pressure loads.
7. Outer Sheath
  • New special sandwich construction for optimum flexibility, abrasion resistance and heavy load special rubber compound.
8. Colour
  • Red

Price Enquiry

Technical Data

Electrical Data

Current-carrying capacity in ampere [A] at 30ºC ambient temperature (acc. DIN VDE 0298-4) on ground:

Cross Section [mm²] up to 10kV [A] over 10 kV [A]
25 131 139
35 162 172
50 202 216
70 250 265
95 301 319
120 352 371
150 404 428
185 461 488
240 553 587

Short Circuit Current

(80 - 250ºC / l = 149 A / mm² ) in kA
mine reeling cable R-(n) TSCGEWTOEUS

Cross Section [mm²] for 1 s (tks) for 0.5 s (tk)
25 3.7 5.3
35 5.2 7.4
50 7.5 10.5
70 10.4 14.8
95 14.2 20.0
120 17.9 25.3
150 22.4 31.6
185 27.6 39.0
240 35.8 50.6

Bending Radii

Smallest permissible bending radius:

Application Diameter
Fixed Installation 6 x outer ø
Reeling Application 12 x outer ø
Deflection Pulleys 15 x outer ø
min. Distance with S-type directional changes 20 x outer ø

Thermal Properties

Permissible temperature on cable surface:

Type Temp
Static -50ºC/+80ºC
Flexing -35ºC/+80ºC
Max. conductor temperature 90ºC
Max. short-circuit temperature of conductor 205ºC

Correction factor for ambient temperatures other than 30ºC to be applied to the current-carrying capacities for cables in the air acc. DIN VDE 0298-4 (permissible conductor temperatures 90ºC)

10ºC -20ºC -30ºC -40ºC -50ºC -60ºC -70ºC
1.15 1.08 1.00 0.91 0.82 0.71 0.58

Correction factor for reeled flexible cables

No. of Layers 1 2 3 4 5
Factor 0.80 0.61 0.49 0.42 0.38
Monospiral reel 0.80

1) DIN VDE 0298-4 Application of cables and cord in power installations: Part 4: recommended current-carrying capacity for sheathed and non-sheathed cables for fixed wirings in and around buildings and for flexible cables and cords.